KT KT356G Intelligent Heat Exchange Unit Controller Scheme Manual

The KT356G intelligent heat exchange unit controller is a product with fully automatic unmanned control function. It can control the operation of circulating pumps, water replenishment pumps, and temperature regulating valves, and provides a communication interface for connection with a computer to display data and perform operations.


KT KT356G Intelligent Heat Exchange Unit Controller Scheme Manual - cover page
Brand
K&T
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
464 KB
Updated
28 September, 2023
MD5 checksum
34E636319A1B74C28143AD83E9FD97A7

About this manual

The KT356G Intelligent Heat Exchange Unit Controller Scheme Manual details the system configuration for automatic control of heat exchange units, including circulation pumps, makeup pumps, and temperature regulating valves. It outlines specific operational scenarios, such as a system with two 0.75kW makeup pumps and three 4kW circulation pumps, defining their start/stop logic, frequency conversion modes, and pressure/temperature targets. This manual is written in Chinese.

What's inside

  • System Configuration
  • Electrical Diagrams
  • Inverter Settings
  • Controller Parameter Settings
  • Application Cases
  • Terminal Wiring
  • Sensor Settings
  • Auxiliary Settings
  • Time Switch Settings

Specifications

Makeup Pump Power2 x 0.75kW
Circulation Pump Power3 x 4kW
Temperature Target65℃
Target Pressure0.4MPa
Relay Switching Time4 hours
Temperature Transmitter Range0-100℃
Pressure Transmitter Range0-1MPa
Tank Level Range0-2m

Frequently asked questions

What is the switching time for the circulation pumps?

The relay switching time for the circulation pumps is set to 4 hours.

How does the system handle power outages?

If power is lost, the control system automatically starts up again 10 seconds after power is restored.

Can the controller be operated manually?

Yes, the control cabinet must have a manual direct pump start function available.