Error, fault and alarm codes of products - what each code means, its causes and what to do - read from the manufacturers’ manuals, with the manual page each answer comes from.
DRV COIL SHORTED indicates drive contactor coil is shorted or damaged cable, requiring RBCU replacement. The manual's first action is: “Replace RBCU”
BYP COIL SHORTED means the bypass contactor coil is shorted, requiring RBCU replacement. The manual's first action is: “Replace RBCU”
PH C CURR FBK indicates loose CT connection on phase C current feedback. The manual's first action is: “Check J2 connector for proper seating”
PH A CURR FBK indicates loose CT connection on phase A current feedback. The manual's first action is: “Check J2 connector for proper seating”
PHASE SEQ means phase sequence is unknown at wiring time, requiring wire swap. The manual's first action is: “Swap any two of the three input wires to the bypass unit”
DRIVE LINK FAULT indicates a bad cable or connection between drive and RBCU (connector J3). The manual's first action is: “Proper seating of cable in drive and RBCU (connector J3)”
MAX CYCLE FAULT means hysteresis band levels are too tight, requiring adjustment of time delays. The manual's first action is: “Check parameters 3202-3205. Increase time delays on parameters 3204 and 3205”
MTR UNDERLOAD indicates a broken belt causing underload condition on the motor. The manual's first action is: “Check load Reset bypass keypad Check fault code 17 on page 25, for further action”
EARTH FAULT indicates an earth fault detected in the motor. The manual's first action is: “Refer to the fault code 16 on page 25.”
COIL POW SUPPLY means there is an internal failure on RBCU or a shorted contactor coil. The manual's first action is: “Cycle power on bypass unit. If contactor coil is shorted, fault 3023 or 3024 will be generated. If…
DRIVE 1ST START indicates the drive has started but bypass mode cannot be entered yet. The manual's first action is: “Run bypass unit in drive mode before attempting bypass mode”
INP PHASE C LOSS means phase C input is lost due to loose connector, wiring issue, or blown fuse. The manual's first action is: “Check J7 connector Check red on input block Check incoming voltage, phase to ground”
INP PHASE B LOSS indicates phase B input is lost due to loose connector, wiring issue, or blown fuse. The manual's first action is: “Check J7 connector Check black wire on input block Check incoming voltage, phase to …
INP PHASE A LOSS means phase A input is lost due to loose connector, wiring issue, or blown fuse. The manual's first action is: “Check J7 connector Check yellow wire on input block Check incoming voltage, phase to gro…
BYPASS COIL OPEN indicates the M2 contactor will not close when commanded due to loose wires or bad output on RBCU. The manual's first action is: “Verify that J8 connector is firmly seated.”