RESERVED is not used on this product. The manual lists no action for this code.
OVERSPEED means motor speed exceeds 120% of the larger of minimum or maximum speed parameters, possibly due to incorrect settings or inadequate braking. The manual's first action is: “Check for and correct: • Paramete…
ENCODER ERR means the drive cannot detect a valid encoder signal due to connection issues, logic level problems, or faulty encoder. The manual's first action is: “Check for and correct: • Encoder presence and proper c…
SUPPLY PHASE indicates ripple voltage in DC link is too high due to missing phase, blown fuse, or external filter interaction. The manual's first action is: “Check for and correct: • Missing mains phase. • Blown fuse.…
CURR MEAS means current measurement is out of range, indicating an internal fault in the drive's current sensing system. The manual's first action is: “Contact your local ABB sales representative.”
OPEX PWR indicates an internal fault due to low voltage condition on the OINT power supply. The manual's first action is: “Contact your local ABB sales representative.”
OPEX LINK means a communication problem has been detected on the fiber optic link between OITF and OINT boards. The manual's first action is: “Contact your local ABB sales representative.”
THERM FAIL indicates an internal fault where the thermistor measuring drive temperature is open or shorted. The manual's first action is: “Contact your local ABB sales representative.”
UNDERLOAD means the motor load is lower than expected, possibly from disconnected load or incorrect user load curve settings. The manual's first action is: “Check for and correct: Disconnected load. Group 37: USER LOA…
EARTH FAULT means a possible ground fault is detected in motor or cables, possibly due to wiring issues or improper grounding. The manual's first action is: “Possible corrections: Check for/correct faults in the input…
EXTERNAL FLT 2 indicates a digital input defined for second external fault has been activated. The manual's first action is: “See parameter 3004 EXTERNAL FAULT 2.”
EXTERNAL FLT 1 indicates a digital input defined for first external fault has been activated. The manual's first action is: “See parameter 3003 EXTERNAL FAULT 1.”
MOTOR STALL means the motor is stalled from excessive load, insufficient power, or incorrect parameter settings. The manual's first action is: “Check for and correct: Excessive load. Insufficient motor power. Paramete…
ID RUN FAIL indicates the motor ID run was not completed successfully due to mismatched motor parameters or connections. The manual's first action is: “Check for and correct: Motor connections Motor parameters 9905...…
PANEL LOSS means panel communication is lost, either due to local control mode or remote mode with parameterized start/stop functions. The manual's first action is: “To correct check: Communication lines and connectio…