START ENABLE 1 alarm happens when a start command is given but the RUN Enable condition is not satisfied. The manual's first action is: “Run Enable condition is not satisfied. Bad 24v supply Bad digital input 24 V com…
OVRD2 BYP alarm occurs when override mode 2 is active and the bypass is controlling the motor. The manual's first action is: “Check Parameter 0103 and 0104 for digital input status”
OVERRIDE 1 alarm is triggered when override mode 1 is active. The manual's first action is: “Check Parameter 0103 and 0104 for digital input status”
INP VOLTAGE LOW indicates the 3-Phase input voltage is too low to enable parameter editing after power-up. The manual's first action is: “Loose J7 connector Low input voltage. Incoming voltage has not reached at least…
DRIVE SETUP error occurs due to incorrect parameter settings. The manual's first action is: “Set Parameter 1001 to "COMM"”
PCB TEMP indicates the RBCU unit has reached a critical temperature due to cooling failure or ambient heat. The manual's first action is: “Stop drive and let cool down and restart Add additional cooling Replace RBCU”
Selected by PAR 1620: RUN ENABLE DAMPER END VALVE OPENING PRE-LUBE CYCLE means the "Run Enable" condition is not satisfied or power supply is faulty. The manual's first action is: “Check 24 Volts on RBCU unit Check fo…
EXT COMM ERR occurs when fieldbus message timing exceeds timeout or communication settings are incorrect. The manual's first action is: “Check Group 51& 53 Tighten Connections Check Communication Cable Grounding”
AUTO TRANSFER indicates the drive has faulted and switched to bypass mode as configured. The manual's first action is: “Check drive”
INP PHASE C LOSS occurs when phase C input is lost, often due to loose wiring or voltage issues. The manual's first action is: “Check J8 connector Check red wire on input block Check incoming voltage, phase to ground”
INP PHASE B LOSS occurs when phase B input is lost, often due to loose wiring or voltage issues. The manual's first action is: “Check J8 connector Check black wire on input block Check incoming voltage, phase to ground”
INP PHASE A LOSS occurs when phase A input is lost, often due to loose wiring or voltage issues. The manual's first action is: “Check J8 connector Check yellow wire on input block Check incoming voltage, phase to ground”
UNKNOWN BYPASS indicates that the bypass configuration is invalid or unsupported. The manual's first action is: “Replace RBCU or load most current firmware Contact ABB at 1-800-HELP-365 option 4 Replace RBCU or load m…
UNKNOWN DRIVE means the drive rating is not recognized by the bypass software. The manual's first action is: “Drive does not match drives configured in bypass RBCU Replace RBCU or reload with most current firmware”
UNKNOWN CB means the bypass control board type is unrecognized and firmware compatibility is required. The manual's first action is: “Firmware is not compatible with control board in RBCU. Firmware 93F and greater com…