The drive has lost communication with the fieldbus network due to a timeout condition. The manual's first action is: “Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communicati…
The drive has blocked a direction change attempt because the system is not permitted to reverse direction at this time. The manual's first action is: “Either: • Do not attempt to change the direction of motor rotation…
The drive has detected a low voltage condition because the under voltage controller is active. The manual's first action is: “Check for and correct: • Undervoltage on mains.”
The drive has detected an overvoltage condition because the over voltage controller is active. The manual's first action is: “Check for and correct: • Static or transient overvoltages in the input power supply. • Insu…
The drive has detected excessive current flow due to the current limiting controller being active. The manual's first action is: “Check for and correct: • Excessive motor load. • Insufficient acceleration time (parame…
PAR PFA IO 3 indicates insufficient digital inputs are available to allocate interlocks for each PFA motor. The manual lists no action for this code.
PAR PFA IO 2 means the actual number of PFA motors does not match those configured in Group 14 or the autochange interval parameter. The manual lists no action for this code.
PAR PFA IO 1 indicates incomplete I/O configuration for PFA, specifically a mismatch between auxiliary motor count and autochange interval settings. The manual's first action is: “Or, a conflict exists between Group 1…
PAR OVERRIDE PAR5 occurs when override mode is enabled but parameters conflict, particularly with 1701 or 1702/1703 values. The manual's first action is: “Verify that 1701 is not zero, and (depending on 9904 value) 17…
PAR PFA OVERRIDE means both override mode and PFA (Programmable Fieldbus Architecture) are active simultaneously, which is incompatible. The manual's first action is: “These modes are mutually incompatible, because PF…
PAR PCU1 occurs when motor nominal frequency or speed parameters are inconsistent with power control settings. The manual's first action is: “Improper motor nominal frequency or speed. Check for both of the following:…
PAR PFAWOSCALAR indicates that motor control mode must be scalar for speed, but it's not set correctly when PFA is enabled. The manual's first action is: “9904 MOTOR CTRL MODE must be = 3 (SCALAR: SPEED), when 8123 PF…
PAR FBUSMISSING occurs when fieldbus control parameters are set but communication protection selection is not active. The manual's first action is: “A parameter is set for fieldbus control (e.g. 1001 EXT1 COMMANDS = 1…
EXT ROMISSING means an extension relay module is missing and outputs have non-zero values. The manual's first action is: “Extension relay module not connected and 1410...1412 RELAY OUTPUTS 4...6 have non-zero values.”
PAR PCU 2 occurs when power control parameters are inconsistent, likely due to incorrect motor nominal kVA or power settings. The manual's first action is: “Improper motor nominal kVA or motor nominal power. Check for…