Error, fault and alarm codes of products - what each code means, its causes and what to do - read from the manufacturers’ manuals, with the manual page each answer comes from.
STACK OVERFLOW means the program cycle has exceeded its memory capacity. The manual's first action is: “Contact ABB with information that preceded fault Cycle Power Replace RBCU”
T3 OVERLOAD indicates that the T3 program cycle is overloaded. The manual's first action is: “Contact ABB with information that preceded fault Cycle Power Replace RBCU”
T2 OVERLOAD indicates that the T2 program cycle is overloaded. The manual's first action is: “Contact ABB with information that preceded fault Cycle Power Replace RBCU”
T1 OVERLOAD indicates that the T1 program cycle is overloaded. The manual's first action is: “Contact ABB with information that preceded fault Cycle Power Replace RBCU”
PMAP FILE means the parameter file is corrupt and needs to be reset or replaced. The manual's first action is: “Cycle Power Contact ABB with information that preceded fault”
SFLASH CORRUPT means there is an internal checksum error in the flash memory. The manual's first action is: “Cycle power Replace RBCU Upgrade firmware”
FBA PAR CONF indicates incorrect Group 51 parameter settings. The manual's first action is: “Verify Group 51 parameters”
NO DRIVE DATA occurs when the drive and bypass have improper connections or communication settings. The manual's first action is: “Proper seating of cable in drive and RBCU (connector J3)”
PCB TEMP means the cabinet cooling has failed or ambient conditions are too high. The manual's first action is: “Stop drive and let cool down and restart”
MTR PHASE indicates an internal, cable, or motor problem. The manual's first action is: “Check wiring in E-Clipse Unit”
EFB 1...EFB 3 means Bacnet device object instances exceed limit in specified parameters. The manual's first action is: “Check Parameters 5011, 5017 and/or 5311, 5317”
FORCE TRIP indicates the E-Clipse unit was tripped by an overriding control system via fieldbus. The manual's first action is: “Check Overriding Control System”
EFB CONFIG FILE means an internal startup error occurred during configuration. The manual's first action is: “Cycle Power Replace RBCU”
EXT COMM LOSS indicates communication issues due to incorrect settings, poor connections, or noise on the line. The manual's first action is: “Check Group 51 & 53 Tighten Connections Check Communication Cable Grounding”
INVALID SUB ASM means an incompatible RBCU unit was installed after firmware change. The manual's first action is: “Contact ABB at 1-800-HELP-365 Option 4”