This quick guide provides essential steps for the installation and setup of the Vacon 20 frequency converter, including safety warnings and mechanical…
This document serves as a quick guide for the installation and setup of the Vacon 20 AC drive. It outlines essential steps for mounting the unit, connecting power and motor cables, and performing a basic Quick Modbus setup. The guide emphasizes safety precautions, noting that only a competent electrician should perform electrical installations and highlighting specific risks regarding live components and earth leakage currents.
The document includes detailed mechanical installation instructions for various models (MI1-MI5), covering screw, DIN-rail, and flange mounting options with specific spacing requirements. It also provides cabling diagrams for power connections and lists technical specifications, including power ratings, nominal input currents, and mechanical dimensions for different voltage series (115V, 380-480V, and 600V).
| Mains voltage (1~ series) | 115 V, 50 / 60 Hz |
|---|---|
| Mains voltage (3~ series) | 380 - 480 V, 50 / 60 Hz |
| Earth leakage current | Exceeds 3.5 mA AC |
| Power rating (MI1, 380-480V) | 0.37 kW (0.5 HP) |
| Power rating (MI5, 380-480V) | 18.5 kW (25 HP) |
| Power rating (MI3, 600V) | 5.5 kW (7.5 HP) |
Only a competent electrician is allowed to carry out the electrical installation.
The tightening torque for power cables is 0.5 - 0.6 Nm (4-5 in.lbs).
You must leave free space for cooling of 100 mm above the Vacon 20.