The MRLDS-450 refrigerant gas detector is designed for use in refrigeration applications and may be used as a stand-alone device, or connected to a facility’s building management system (BMS). It enables compliance with refrigerant safety codes (ASHRAE 15 and EN378) and features audible and visual alarms to alert personnel in the event of a refrigerant leak.
The Emerson MRLDS-450 is a refrigerant gas detector designed for use in refrigeration applications, such as machinery rooms, cold rooms, and freezers. It features audible and visual alarms to alert personnel of refrigerant leaks and can operate as a stand-alone device or connect to a building management system (BMS). The device ensures compliance with refrigerant safety codes ASHRAE 15 and EN378.
| Dimensions | 6.5" x 6.5" x 3.4" (165 x 165x 87 mm) |
|---|---|
| Weight | 1.05 lbs (480g) |
| Alarm Delay | 0 to 15 minutes |
| Analog Output | 4 to 20 mA, 0 to 5V, 0 to 10V, 1 to 5V (default) or 2 to 10V |
| Bluetooth | Bluetooth Low Energy, BLE 4.2 |
| Modbus Baud Rate | 9,600 (default) or 19,200 |
| Power Supply | 19.5 to 28.5 VDC or 24 VAC ±20% |
| Operating Temperature (Semiconductor) | -40°F to 122°F (-40°C to 50°C) |
| Operating Humidity | 5 to 90% RH, non-condensing |
| Operating Pressure | 23.6 to 32.5"Hg (800 to 1,100 mbar) |
No, the MRLDS-450 is NOT certified or approved for operation in oxygen-enriched atmospheres.
No, the device has not been designed to be intrinsically safe for use in areas classified as being hazardous locations.
The default passkey is 123456.
The default unlock code is 1234.