SmartGen HAT160 ATS Controller User Manual

HAT160 ATS Controller User Manual, introduces the features, performance, specifications, panel description, operation, etc. of the controller.


SmartGen HAT160 ATS Controller User Manual - cover page
Brand
Smartgen
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
17
File format
PDF
File size
1.2 MB
Published
17 November, 2023
Updated
17 November, 2023
MD5 checksum
0E07095DAEED6820634908D6A7867B8A

About this manual

The SmartGen HAT160 ATS Controller is designed for single motor CB ATS to accurately detect 2-way-3-phase 4-wire or single-phase 2-wire voltage abnormalities. It controls the ATS by detecting over/under voltage, frequency issues, and phase loss, and can send signals to start a genset upon abnormal I# power. The device supports remote communication and parameter configuration via the LINK port.

What's inside

  • Overview
  • Performance and Characteristics
  • Specification
  • Panel Description
  • Alarm
  • Connection
  • Parameters Setting
  • Typical Application
  • Troubleshooting

Specifications

Operating VoltageAC240V (range: AC170V~277V)
Power ConsumptionNot more than 2VA
AC Voltage InputAC170V – AC277V
AC Frequency50/60Hz
Case Dimensions86.9mmx158mmx119.5mm
Panel Cutout73.5mmx144mm
Working Temperature-25~+70°C
Protection LevelIP55
Weight0.6kg

Frequently asked questions

What voltage range does the HAT160 controller support?

The controller supports an operating voltage range of AC170V to AC277V.

How do I enter the parameter configuration mode?

Press the Auto/Manual button for 5 seconds to enter the parameter configuration mode.

What happens if the controller detects a close failure?

If the controller cannot detect a close signal when the close delay ends, it is regarded as a close failure and the alarm indicator illuminates.

Download PDF (1.2 MB)

More Smartgen Manuals


View all Smartgen manuals →