Installation Instructions for Micro Motion ™ ELITE ™ Coriolis Flow and Density Sensor
This document describes planning, mounting, wiring, and grounding for Micro Motion ELITE Coriolis flow and density sensors. It includes an installation checklist, best practices, temperature limits, and mounting options for specific sensor models.
It also covers transmitter output and I/O wiring, cable connection and maximum cable lengths, grounding, and supplementary procedures such as sensor case purging and pressure relief. This manual is written in Japanese.
| Micro Motion 9-wire cable maximum length with 9739 MVD transmitter | 305 m |
|---|---|
| Micro Motion 9-wire cable maximum length with other MVD transmitters | 18 m |
| Micro Motion 4-wire cable maximum length | 305 m non-hazardous; 152 m IIC hazardous; 305 m IIB hazardous |
| User-supplied 4-wire power cable maximum length, 0.326 mm² | 91 m |
| User-supplied 4-wire power cable maximum length, 0.518 mm² | 152 m |
| User-supplied 4-wire power cable maximum length, 0.823 mm² | 305 m |
| User-supplied 4-wire signal cable maximum length, RS-485 | 305 m for 0.326 mm² or larger |
| Ambient temperature for electronics | Not usable below -40 °C or above 60 °C |
| CMFS007 process fluid and case average temperature difference | Within 99 °C |
The maximum length is 305 m.
No. The electronics cannot be used when the ambient temperature is below -40 °C or above 60 °C.
No. Micro Motion sensors have no straight-pipe-length requirement.
Liquid and slurry should flow upward through the sensor.