Smartgen HAT220A/HAT240A Dual Power Automatic Switching Controller User Manual

HAT220A/HAT240A dual power automatic switching controller user manual, introduces the performance, features, technical parameters, panel operation, programmable parameters, operation control, wiring terminal functions, typical application diagrams, external dimensions and installation dimensions, common faults and troubleshooting methods.


Smartgen HAT220A/HAT240A Dual Power Automatic Switching Controller User Manual - cover page
Brand
Smartgen
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
10
File format
PDF
File size
695 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
C5F7E2B80351B8431C7BC589D19A418A

About this manual

Smartgen HAT220A/HAT240A is a dual power automatic switching controller built around a microprocessor. It detects two three-phase voltages, two single-phase voltages, or two two-phase voltages, judges voltage abnormalities such as loss of power, overvoltage and undervoltage, and after a delay controls ATS switching. It also provides a generator start signal after an abnormal supply delay.

The Chinese user manual covers features, technical specifications, panel operation, delay adjustment and restoring factory delay values, programmable parameters and ranges, operation control, wiring terminal functions, typical application diagrams, dimensions and troubleshooting. It lists factory delay settings and describes priority settings for supply I, supply II or no priority. This manual is written in Chinese.

What's inside

  • Overview
  • Features
  • Technical Specifications
  • Panel Operation
  • Delay Adjustment
  • Restore Factory Delay Values
  • Programmable Parameters and Ranges
  • Operation Control
  • Wiring Terminal Functions
  • Troubleshooting

Specifications

Rated input voltage and frequency, three-phase380 V AC, 50/60 Hz, three-phase four-wire
Rated input voltage and frequency, single-phase (HAT240A)230 V AC, 50/60 Hz, single-phase two-wire
Overvoltage threshold264 V (phase voltage)
Undervoltage threshold172 V (phase voltage)
AC voltage measurement accuracy2%
AC phase voltage measurement range(160–300) V ±20%
Closing time5 s
Power consumption≤ 2 VA
Operating temperature-30 to +70 °C
Humidity20–95%
Net weight0.47 kg
Switch output relay contact capacity16 A 250 VAC / 16 A 28 VDC
Generator start relay contact capacity7 A 250 VAC / 7 A 28 VDC

Frequently asked questions

What are the factory settings for abnormal supply delay and generator stop delay?

The factory setting for abnormal supply delay on supplies I and II is 5 seconds, and the generator stop delay is 90 seconds.

What supply priority modes can be set?

Supply I priority, supply II priority, and no priority can be set.

Can the voltage upper and lower limits be set from the panel?

No. The voltage upper and lower limits can only be programmed through a PC.

What should be checked if the controller has no response when powered?

Check the controller wiring.