This document is the quick start guide for DOP-B series HMI, which introduces the product's features and installation, connection and operation instructions
This guide provides step‑by‑step instructions for installing the Delta DOP‑B series human‑machine interface (HMI). It includes safety precautions, wiring recommendations, mounting procedures, and basic inspection checks to ensure reliable operation.
The document also details the serial and Ethernet communication ports, part identification, and environmental storage limits, helping installers configure the device correctly and maintain it over its service life.
| Flash ROM | 128 MB (OS System) |
|---|---|
| SDRAM | 64 Mbytes |
| Power Input | DC +24 V (‑10 % ~ +15 %) |
| Operating Temperature | -20 °C to +60 °C |
| Relative Humidity | 10 % to 90 % (non‑condensing) |
The mounting screws should be tightened to a torque of 0.7 N·m.
Ground resistance should not exceed 100 Ω.
Shielded twisted‑pair cables should be used for all wiring.
Turn the power off before changing the backup battery; all data will be cleared after the change.