Encoder feedback loss warning occurs when encoder signal is lost and inverter may switch to sensorless vector control, with specific conditions for configuration errors. The manual's first action is: “Check also alarm…
Inverter OverTemperature is triggered if heat sink or chip junction temperatures exceed warning levels, prompting reduced pulse frequency. The manual's first action is: “- Ambient temperature must lie within specified…
UnderVoltage Limit occurs when main supply fails, causing DC-link voltage to fall below specified limits. The manual lists no action for this code.
Overvoltage limit occurs during ramp down if Vdc controller is disabled (P1240 = 0), or permanently indicates input voltage issues. The manual lists no action for this code.
Current Limit is triggered when motor power does not match inverter power, leads are too long, or there’s an earth fault. The manual lists no action for this code.
Motor Stalled occurs due to rapid ramp rates in SLVC/VC mode, running onto a spinning motor without flying start enabled, or excessive load at very low frequency. The manual's first action is: “Quit fault eg. via D12”
Belt Failure is triggered when load conditions indicate belt failure or mechanical fault, typically during low torque/speed events. The manual's first action is: “Quit fault eg. via D12”
Acceptance Test / Confirmation pending occurs after a Powermodul or Control Unit swap or startup clone, indicating parameters may need verification before operation. The manual's first action is: “The parameterset aft…
Configuration vector for the drive failed indicates that either hardware or software configuration does not match during startup, causing a trip. The manual's first action is: “Internal Failures can not be fixed.”
PID Feedback above max. Value occurs when the PID feedback signal exceeds the maximum value set in parameter p2267. The manual's first action is: “Change value of p2267. Adjust feedback gain.”
PID Feedback below min. Value happens when the PID feedback signal falls below the minimum value set in parameter p2268. The manual's first action is: “Change value of p2268. Adjust feedback gain.”
Watchdog Reset occurs due to a software error requiring replacement of the inverter control unit. The manual's first action is: “Contact Service Department. Change inverter control unit.”
Encoder feedback loss indicates the encoder signal has been lost, either due to a complete signal failure or sudden speed change exceeding set limits. The manual lists no action for this code.
External Fault occurs when an external fault is triggered via command input using control word 2, bit 13. The manual's first action is: “Check P2106.”
AI lost Input Signal indicates either a broken wire or signal out of limits for an analog input channel. The manual lists no action for this code.