Alarm codeErr-12
Overcurrent alarm triggers due to prolonged operation with excessive rated torque, bad grounding, or damaged motor insulation. The manual's first action is: “Reduce the load or change a motor with a bigger motor.”
- Model
- GSK GS2000T Series
- Display shows
- Alarm for overcurrent (Err-12)
- Type
- Alarm code
- Source
- Manual p. 121
What Err-12 means
Alarm for overcurrent p. 121
Common causes
- 1. Motor runs for long time with the excessive rated torque; p. 121
- 2. The grounding is bad; p. 121
- 3. The motor's insulation is damaged. p. 121
What to do
- Reduce the load or change a motor with a bigger motor. p. 121
- Ensure the grounding resistor must be less than 10Ω. p. 121
- Change a motor. p. 121
If Err-12 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact GSK service.
This page summarises what the manufacturer’s manual says about Err-12; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with GSK. Found a mistake? Report an error.