GSK GS2000T Series Error Err-6: Speed amplifier saturation failure

AC servo drive unit · taken from the manufacturer’s manual, pages cited

Alarm codeErr-6

Speed amplifier saturation failure occurs when U,V,W phases are reversed, motor parameters are incorrect, or torque limitation is too small and rigidity is insufficient. The manual's first action is: “Connect correctly U,V,W.”

Model
GSK GS2000T Series
Display shows
Speed amplifier saturation failure (Err-6)
Type
Alarm code
Source
Manual p. 119

What Err-6 means

Speed amplifier saturation failure p. 119

Common causes

  • 1. U,V,W phase are connected reversely; p. 119
  • 2. The motor's default parameter is wrong or the motor's characters are bad; p. 119
  • 3. The torque limitation is too small and the motor rigidity is not enough; p. 119
  • 4. The mechanical device connected with the motor shaft is blocked, which p. 119

What to do

  1. Connect correctly U,V,W. p. 119
  2. Check the motor model code corresponding to PA1, and call correctly the motor's default parameter. p. 119
  3. Increase the torque limitation value (PA133~PA136) to increase its rigidity. p. 119
  4. Resolve the mechanical fault. p. 119

If Err-6 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact GSK service.