Alarm codeErr-6
Speed amplifier saturation failure occurs when U,V,W phases are reversed, motor parameters are incorrect, or torque limitation is too small and rigidity is insufficient. The manual's first action is: “Connect correctly U,V,W.”
- Model
- GSK GS2000T Series
- Display shows
- Speed amplifier saturation failure (Err-6)
- Type
- Alarm code
- Source
- Manual p. 119
What Err-6 means
Speed amplifier saturation failure p. 119
Common causes
- 1. U,V,W phase are connected reversely; p. 119
- 2. The motor's default parameter is wrong or the motor's characters are bad; p. 119
- 3. The torque limitation is too small and the motor rigidity is not enough; p. 119
- 4. The mechanical device connected with the motor shaft is blocked, which p. 119
What to do
- Connect correctly U,V,W. p. 119
- Check the motor model code corresponding to PA1, and call correctly the motor's default parameter. p. 119
- Increase the torque limitation value (PA133~PA136) to increase its rigidity. p. 119
- Resolve the mechanical fault. p. 119
If Err-6 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact GSK service.