A forward limit switch error occurs when the forward limit switch is activated or the drive is overloaded. The manual's first action is: “Check if there is overload or the motor current is too high. Increase motor capacity or reduce load.”
- Model
- Delta ASDA-B series
- Display shows
- Forward limit switch error (ALE 16)
- Type
- Error code
- Source
- Manual p. 256
What ALE 16 means
Forward limit switch error p. 263
Common causes
- Forward limit switch is activated. p. 263
- The temperature of IGBT is over high. p. 263
- The drive has exceeded its rated load during continuous operation. p. 263
- Short-circuit at drive output. p. 263
What to do
- Check if there is overload or the motor current is too high. Increase motor capacity or reduce load. p. 263
- Check the drive input wiring. Ensure all wiring is correct. p. 263
- Turn ARST (DI signal) ON to clear the fault or restart the servo drive. p. 263
Before you service the product, read the safety instructions in the manual p. 3.
If ALE 16 is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.
This page summarises what the manufacturer’s manual says about ALE 16; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.