Delta ASDA-B series Error ALE 18: Memory error

Delta ASDA-B series · taken from the manufacturer’s manual, pages cited

Error codeALE 18

The memory error occurs when there is an error in EE-PROM write-in or read-out, or the RS-232/485 serial communication times out due to incorrect parameter settings. The manual's first action is: “Check communication time out parameter setting. Correctly set P3-07.”

Model
Delta ASDA-B series
Display shows
Memory error (ALE 18)
Type
Error code
Source
Manual p. 256

What ALE 18 means

Memory error p. 263

Common causes

  • EE-PROM write-in and read-out is in error. p. 263
  • RS-232/485 serial communication time out p. 263
  • Setting value in time out parameter is not correct. p. 263
  • Not receiving communication command for a long time. p. 263

What to do

  1. Check communication time out parameter setting. Correctly set P3-07. p. 263
  2. Check whether communication cable is loose or broken. Tighten the communication cable, make sure the communication cable is not damaged and ensure all wiring is correct. p. 263
  3. Turn ARST (DI signal) ON to clear the fault. This fault message can also be removed automatically after the communication is normal. p. 263

Before you service the product, read the safety instructions in the manual p. 3.

If ALE 18 is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.

This page summarises what the manufacturer’s manual says about ALE 18; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.