Pentair ECS Series Differential Pressure Pulse Controller User Manual

This manual covers the Pentair ECS Series intelligent differential pressure pulse controller, including specifications, installation, and operation.


Pentair ECS Series Differential Pressure Pulse Controller User Manual - cover page
Brand
Pentair
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
5
File format
PDF
File size
2.5 MB
Published
19 October, 2026
Updated
19 October, 2026
MD5 checksum
D2DA8524B28DA4E4223C992991363856

About this manual

The Pentair ECS Series intelligent differential pressure pulse control system is designed to extend filter bag life and reduce dust collector operating costs. It features a main controller and optional expansion boards, allowing for up to 360 output points to control multiple pulse valves. The system automatically determines the optimal cycle for blowing off filter bags based on differential pressure. This manual is written in Chinese.

What's inside

  • Overview
  • Product Features
  • Technical Parameters
  • Installation Precautions
  • Main Board Description
  • Expansion Board Description
  • Terminal Connections
  • Ordering Codes

Specifications

Differential Pressure Range0 ~ 4.5 kPa
Input Voltage AC100/240 V @ 50/60 Hz
Output Voltage ACSame as input voltage
Max Input Power AC In/AC Out235 W
Max Input Power AC In/DC Out65 W
Total Output Points360
Operating Temperature-40°C to 60°C
Protection RatingIP 66/67, NEMA 1, 4, 4X, 6, 12 & 13

Frequently asked questions

How many output points can the ECS system provide?

The system can provide up to 360 output points by connecting the main board with up to 29 expansion boards.

What is the maximum number of pulse valves one AC output port can control?

Each AC output port can control up to 10 pulse valves.

What is the maximum number of pulse valves one DC output port can control?

Each DC output port can control up to 2 pulse valves.

Does the ECS controller have a built-in differential pressure transmitter?

Yes, the controller comes with a built-in differential pressure transmitter to intelligently determine the best cycle for blowing off filter bags.

Download PDF (2.5 MB)