Specification sheet for the Lutron GRX-TVM2 Ten Volt Module (TVM) and HW-TVMKIT-120/230 kits used with HomeWorks QS systems.
This Lutron specification sheet covers the GRX-TVM2 Ten Volt Module (TVM) and the HW-TVMKIT-120 and HW-TVMKIT-230 Ten Volt Module kits for HomeWorks QS systems. The GRX-TVM2 is treated as an output module and controls load types such as 0–10 V link, 0–10 V power, PWM, DALI (broadcast only) and Tridonic DSI with a module interface (MI). Each TVM has two independently configurable outputs and can work with RPM-4U module outputs to switch ballasts or drivers.
Each HW-TVMKIT supports up to 12 TVMs (24 circuits per panel total) and includes an ISO2 isolator that provides independent power of up to 750 mA. The sheet lists power, capacity and environmental specifications, wiring and installation steps for panels such as HWI-PNL-8, HWAP-8, HWBP-8 and PBK-8, and explains DALI-2 certification requirements for compatible LED drivers and fluorescent ballasts. This manual is written in Chinese.
| GRX-TVM2 power | 12 V- 50 mA per circuit |
|---|---|
| ISO2 output | 24 V~ 50/60 Hz, 750 mA per ISO2 |
| Transformer input (HW-TVMKIT-120) | 120 V~ 50/60 Hz, 40 W |
| Transformer input (HW-TVMKIT-230) | 220 V~ to 240 V~ 50 Hz, 40 W |
| Transformer output | 24 V~ 1.6 A, IEC PELV / NEC Class 2 |
| Capacity per GRX-TVM2 | 2 circuits |
| Capacity per kit | Up to 12 GRX-TVM2 modules |
| Load types | 0–10 V link, 0–10 V power, PWM, DALI (broadcast only), Tridonic DSI with MI |
| Operating temperature | 0 °C to 40 °C (32 °F to 104 °F) |
| Operating humidity | 0%–90% non-condensing, indoor use only |
Each GRX-TVM2 controls 2 circuits, and each HW-TVMKIT supports up to 12 GRX-TVM2 modules.
Each ISO2 provides up to 750 mA, enough for 6 fully loaded TVMs or up to 12 partially loaded TVMs.
DALI LED drivers and fluorescent ballasts must be DALI-2 certified and carry the DALI-2 mark; DALI version 1 devices do not guarantee compatibility and should be tested.
It can be installed in HWI-PNL-8, HWAP-8, HWBP-8 or PBK-8 panels, replacing a remote power module (RPM) 8.