Lutron TVI-LMF-2A EcoSystem to 0-10V Interface Installation Guide

The Lutron EcoSystem to 0-10 V Interface provides a control gateway from an EcoSystem link to a 0-10 V compatible lighting device, typically an LED driver. It allows for individual addressability of the 0-10 V device, but only provides one-way communication from the controls to the 0-10 V device. This interface is for single-fixture control only. For fixtures that have multiple drivers installed (such as two or three drivers being needed to reach certain output wattages), only one interface may be necessary. This interface is not intended for control of multiple fixtures.


Lutron TVI-LMF-2A EcoSystem to 0-10V Interface Installation Guide - cover page
Brand
Lutron
Category
LED Controller
Document type
Installation Guide
Language
English
Pages
12
File format
PDF
File size
328 KB
Published
16 November, 2023
Updated
16 November, 2023
MD5 checksum
3222E432D85924298FE4855574C679F9

About this manual

The Lutron TVI-LMF-2A EcoSystem to 0-10V Interface provides a control gateway from an EcoSystem link to a 0-10V compatible lighting device, typically an LED driver. It allows individual addressability of the 0-10V device with one-way communication from controls to the device, and is designed for single-fixture control only.

The interface operates on 120-277 VAC, consumes up to 1.0 W when the output load is on and 0.5 W in standby, and supports up to 5 drivers with a maximum 2 A load. It includes relay output, 0-10V control sinking up to 25 mA, and a maximum 0-10V wire length of 10 ft (3 m). Installation steps cover mounting, wiring to drivers, mains wiring, and EcoSystem link connection.

What's inside

  • Overview
  • Specifications
  • Step 1: Mount Interface
  • Step 2: Wire Interface to Driver(s)
  • Step 2a: Line Voltage Wiring
  • Step 2b: 0-10V Wiring
  • Step 3: Wire Mains to the Interface
  • Step 4: Wire EcoSystem Link
  • Mounting Dimensions
  • Wiring Diagram

Specifications

Input Voltage120-277 VAC, 50/60 Hz
Maximum Power Consumption (Load On)≤1.0 W
Maximum Power Consumption (Standby)≤0.5 W
Relay Output Rating2 A electronic load, 5 drivers maximum
0-10V Control Current Rating25 mA max (sink only)
Maximum 0-10V Wire Length10 ft (3 m)
0-10V Voltage RangeOff ≤0.5 V, Minimum 1 V, Maximum 10 V
ComplianceIEC 60929 Annex E2
Maximum Connected Load Current2 A

Frequently asked questions

What is the maximum wire length for the 0-10V control wires?

The maximum 0-10V wire length is 10 ft (3 m) from the interface to the driver.

What are the voltage levels for the 0-10V output?

The 0-10V output uses ≤0.5 V for off, 1 V for minimum light level, and 10 V for maximum light level.

What is the power consumption of the interface in standby?

The interface consumes ≤0.5 W when the output load is turned off (standby).