This guide provides detailed information on using LutronR SoftswitchR relay technology to switch 208V loads. The technology ensures that the load is at 0V when it is de-activated.
This document provides guidance on implementing 208 V load switching using Lutron Softswitch relay technology. It details a recommended method that utilizes a two-pole breaker and two Softswitch relay outputs to ensure 0 V potential at the load when deactivated. This approach guarantees an air gap on both switched legs when the load is turned off.
| Relay Technology Life | 1,000,000 cycles |
|---|---|
| Relay Module Capacity | four 16 A relays |
The recommended method uses a two-pole breaker and two Softswitch relay outputs to guarantee 0 V potential at the load when deactivated.
Two-pole switching requires two relays per load, programmed the same to break both phases.