The Eaton HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected loads (HotSwap function).
The Eaton HotSwap Maintenance ByPass (MBP) module allows for the servicing or replacement of an Uninterruptible Power Supply (UPS) without affecting the connected loads. It features a rotary switch with two positions: Normal, where the load is supplied by the UPS, and Bypass, where the load is supplied directly by the AC power source. This ensures continuous power to connected equipment during UPS maintenance or replacement.
| Input Cord | NEMA 5-15P 15A cord (3.3 ft length) |
|---|---|
| Output Sockets | 6 NEMA 5-15R 15A socket outlets |
| Dimensions | 2.1 x 17.3 x 3.8 inches |
| Leakage Current Limit | 3.5 mA |
The switch has two positions: Normal, where the load is supplied by the UPS, and Bypass, where the load is supplied directly by the AC-power source.
Set the switch to the Bypass position and check that the load is still supplied, then set the switch back to the Normal position.
The red LED on the HotSwap MBP module goes ON.
The sum of the leakage currents of the product and the devices it supplies must not exceed 3.5 mA.