PDU8000 Precision PDF-T Quick Guide, introduces the device model description, safety precautions, pre-installation preparation, installation steps, operation steps, maintenance and maintenance of precision power distribution cabinets
The Huawei PDU8000 Precision PDF-T is a precision power distribution cabinet. The quick guide covers safety precautions, local regulations, personnel requirements, human safety, model description, tools, cabinet layout, and installation.
It explains moving and anchoring the cabinet, installing input and output cables, and completing the electrical, hardware, and cable checklists after installation. It also describes powering on and commissioning, including checking the monitoring display unit and switching circuit breakers in sequence.
| Cabinet dimensions (H x W x D) | 2200 mm x 600 mm x 1200 mm |
|---|---|
| Input circuit breaker copper conductor cross-sectional area | 70 mm² |
| Input PE copper conductor cross-sectional area | 35 mm² |
| Input N copper conductor cross-sectional area | 70 mm² |
| Output L copper conductor cross-sectional area | 6 mm² |
| Output PE copper conductor cross-sectional area | 6 mm² |
| Recommended torque for M12 and M16 bolts | 47 N·m (M12); 120 N·m (M16) |
The cabinet dimensions are 2200 mm x 600 mm x 1200 mm (H x W x D).
The recommended torque for M12 bolts is 47 N·m.
Check that all cables are correctly connected, ground cables are securely connected, phase cables are properly connected, and all circuit breakers are OFF.
Cables can be routed in and out from the top.