Describes the contents to be prepared before installing the inverter, including power cables, control cables, and fuses.
This document provides step‑by‑step installation instructions for the ABB ACS580-01 drive series (frame sizes R1 through R9). It covers safety warnings, unpacking, capacitor reforming, cable and fuse selection, site inspection, wall mounting, cover removal, cable box installation, residual voltage labeling, grounding system compatibility, insulation testing, power and control cable connections, and required torque values.
The guide applies to units sold in China and references a separate guide for global sales. It includes dimensional drawings for each frame size, grounding system requirements (TN‑S, corner‑grounded delta, IT, TT), and notes on built‑in brake choppers for frames R1–R3 and external brake choppers for frames R4–R9. This manual is written in Chinese.
| Supported grounding systems | TN‑S (center‑grounded three‑phase), corner‑grounded delta, IT, TT |
|---|---|
| Minimum cable voltage rating | 600 V AC |
| Cable temperature rating (IEC) | 70 °C minimum |
| Cable temperature rating (UL, IP55) | 75 °C minimum |
| Built‑in brake chopper | Frames R1–R3 |
| External brake chopper connection | Frames R4–R9 via UDC+ and UDC‑ |
Wait 5 minutes for the intermediate circuit capacitors to discharge.
ABB recommends symmetrical shielded cable (VFD cable) for both input power and motor cables.
All drive types can be connected to a symmetrically grounded TN‑S system (center‑grounded three‑phase).
Over 100 MΩ.