Emerson FASANI B Type Pressure Self-Sealing Check Valve Installation and Maintenance Manual

This document introduces the storage, transportation, installation and maintenance requirements of FASANI pressure self-sealing check valve - B type swing check valve and inclined plate cast check valve.


Emerson FASANI B Type Pressure Self-Sealing Check Valve Installation and Maintenance Manual - cover page
Brand
Emerson
Category
Industrial Supply
Document type
Installation Guide
Language
Chinese
Pages
4
File format
PDF
File size
346 KB
Published
03 November, 2023
Updated
03 November, 2023
MD5 checksum
EC4C481C60B4507318F9072777F4DF47

About this manual

This Emerson installation and maintenance manual covers the FASANI B type pressure self-sealing check valve, supplied as swing check and inclined plate cast check valve versions (document VCIOM-01628-ZH). It explains how the valves are packed, transported and lifted, how they must be stored before installation, and what preparation and checks are needed before mounting them in a line.

The installation section covers placement in horizontal piping or in vertical piping with upward flow, the recommended orientation shown in Figure 2, and the procedures for butt weld and flanged valves. The manual then gives start-up inspection, the bolt torque values for the pressure seal gasket in Table 1, normal and periodic inspection, a troubleshooting table, and the field procedure for replacing the body gasket; all other repairs are to be carried out by Emerson or its designated service company. This manual is written in Chinese.

What's inside

  • Valve storage and preservation
  • Handling requirements
  • Valve lifting
  • Storage and preservation before installation
  • Preparation before installation
  • Recommended installation positions
  • Installation instructions
  • Valve inspection before start-up
  • Troubleshooting guide
  • Maintenance and gasket replacement

Specifications

Valve typeB type pressure self-sealing check valve, in swing check and inclined plate cast versions
Normal installation positionHorizontal piping; vertical piping is also allowed when flow runs upward
Pressure seal bolt torque (part no. 31)Listed in Table 1 by stud size, from 18 lb-ft / 24.5 N·m
Packaging inspection interval in storageEvery two months
Special tools requiredNone for the maintenance operations described in the manual

Frequently asked questions

How should the FASANI B type check valve be installed?

Check valves are normally installed in horizontal piping, but may also be installed in vertical piping where the flow runs upward; the manual recommends the orientation shown in Figure 2.

Are special tools needed to replace the gasket?

No. The manual states that the maintenance operations it describes do not require special tools.

What should be done after hydrotesting the pipeline?

If the line will stay closed for a long time after the test, depressurize the piping and drain the test water completely.

Download PDF (346 KB)