ABB ACH580 Variable Frequency Drive Override Mode Application Guide

This document is the instruction manual for ABB ACH580 variable frequency drive, which introduces the function and characteristics of the drive and how to use it in emergency situations such as fire in buildings


ABB ACH580 Variable Frequency Drive Override Mode Application Guide - cover page
Brand
ABB
Category
inverter
Document type
Application Note
Language
English
Pages
14
File format
PDF
File size
5.8 MB
Published
03 November, 2023
Updated
03 November, 2023
Model
ACH580
MD5 checksum
578601FC2837DD11189CEFAB6B5D3232

About this manual

This ABB ACH580 application guide describes override mode, also called fireman's override mode, for the ACH580 variable frequency drive. In this mode the drive runs a motor at an adjustable, predefined or PID controlled speed in any direction to assist a building smoke control system during evacuation and firefighting.

Override mode is activated by a single digital input, typically a contact closure from the building's fire alarm system, and the drive then ignores other control inputs and commands. The guide covers the override method of operation, including preset fixed speed, variable speed, closed-loop PID control and floating point control, and explains how faults and interlocks are handled during override operation.

What's inside

  • What is override mode?
  • Override for ACH580
  • Override method of operation
  • Override application examples
  • HVAC units in residential and commercial buildings
  • Evacuation routes in buildings
  • Tunnels
  • Malls, atriums, arenas and similar large volume spaces
  • Benefits for the owners
  • FAQs

Frequently asked questions

How is override mode activated on the ACH580?

It is activated by a single digital input, typically a contact closure from the building's fire alarm system.

What happens to other control inputs during override mode?

The drive ignores other inputs, including analog, digital, serial and keypad commands, and parameters cannot be edited during override mode.

When does the drive exit override mode?

It cannot exit until the fire condition signal is reset by opening the contact closure or removing power from the variable frequency drive.