This file is the instruction manual for the FS-N10 series digital fiber sensor, which introduces the product's use methods, precautions, etc.
The KEYENCE FS-N10 Series Digital Fiber Sensor Instruction Manual explains correct use, UL/C-UL regulatory precautions, included accessories, and the names of main and expansion unit parts. It also gives quick-start procedures for DIN-rail and wall mounting, connecting a fiber unit, and linking multiple amplifiers.
The manual describes calibration methods, including two-point, maximum sensitivity, fully automatic, and positioning calibration, and simple preset functions for setting the current value. It notes that up to 16 expansion units can be connected to one main unit.
| UL File No. | E301717 |
|---|---|
| UL Category | NRKH, NRKH7 |
| Enclosure Type | Type 1 (Based on UL50) |
| Maximum expansion units per main unit | 16 |
| Over current protection device rating | 30 V or more and not more than 1 A |
| Fiber insertion depth | Approximately 14 mm |
Up to 16 expansion units can be connected to one main unit.
Use a power supply with Class 2 output defined in NFPA70 and connect power supply, control input, and control output to a single Class 2 source only.
Insert the fiber unit into the amplifier by approximately 14 mm.
Two-point calibration is the basic method: press the [SET] button once without a workpiece and once with the workpiece.