Toshiba VF-AS1 Inverter Safety Precautions

This document describes the safety precautions for the inverter, including usage limitations, usage instructions, transportation and installation precautions


Toshiba VF-AS1 Inverter Safety Precautions - cover page
Brand
Toshiba
Category
inverter
Document type
User Manual
Language
Chinese
Pages
300
File format
PDF
File size
6.1 MB
Published
30 October, 2023
Updated
30 October, 2023
Model
VF-AS1
MD5 checksum
3DE74C1F9FF446ACFBC6F4EE50D4CE63

About this manual

This document is the safety precautions section of the Toshiba TOSVERT VF-AS1 inverter manual. It explains the meaning of the DANGER and CAUTION indications and the prohibition and mandatory-action icons, then lists the safety rules for the inverter's intended use, handling, transportation and installation, wiring, operation, maintenance and disposal.

The text also notes that the inverter is intended for variable-speed operation of general-purpose industrial three-phase induction motors, gives the procedure for confirming that the DC circuit voltage has fallen to 45 V or less before wiring or inspection, and shows example warning labels for the momentary power interruption restart and retry functions. A short foreword thanks the purchaser and mentions the VFAS1-4355KPC, VFAS1-4400KPC and VFAS1-4500KPC models. This manual is written in Chinese.

What's inside

  • Safety Precautions
  • Usage Notes
  • Transportation and Installation
  • Wiring
  • Operation
  • Momentary Power Interruption Restart and Retry
  • Maintenance and Inspection
  • Disposal
  • Warning Label Instructions
  • Foreword

Specifications

Input voltage tolerance+10%, -15% of the nameplate rated voltage (for continuous use at 100% load: ±10%)
Waiting time after turning off input power15 minutes or more before touching wiring or starting inspection
Safe DC circuit voltage before wiring/inspection45 V or less between PA and PC
Two-person carrying requirementInverters of 30 kW or more (20 kg or more) must be carried by two or more people
Stall prevention level settingDo not set below 30% in normal use

Frequently asked questions

What must be done before wiring or inspection?

Turn off the input power, wait at least 15 minutes and confirm the charge lamp is off, then use a meter rated for DC 800 V or more to confirm the DC circuit voltage between PA and PC is 45 V or less.

What loads can the inverter be used with?

It is intended for variable-speed operation of general-purpose industrial three-phase induction motors; it must not be used with other loads, and use as a permanent magnet motor drive requires a matching test in advance.

How should a large inverter be transported?

Inverters of 30 kW or more (20 kg or more) should be carried by two or more people, and large-capacity inverters should be moved with a crane or similar equipment.

What is prohibited regarding the input power connection?

Do not connect the input power to the inverter output (motor side) terminals U/T1, V/T2 and W/T3, as this damages the inverter and can cause fire.

Download PDF (6.1 MB)