Toshiba VF-AS1 Inverter Instruction Manual
The document is an instruction manual for the Toshiba TosveRT VF-AS1 series of inverters. It covers power ratings from 500V class (1.5~500kW) to 690V class (2.2~630kW). The guide details safety precautions, transportation and installation requirements, wiring procedures, and operational settings.
Read onlineTOSHIBA VF-AS1 specifications
| Input voltage tolerance | +10%, -15% of the nameplate rated voltage (for continuous use at 100% load: ±10%) |
|---|---|
| Waiting time after turning off input power | 15 minutes or more before touching wiring or starting inspection |
| Safe DC circuit voltage before wiring/inspection | 45 V or less between PA and PC |
| Two-person carrying requirement | Inverters of 30 kW or more (20 kg or more) must be carried by two or more people |
| Stall prevention level setting | Do not set below 30% in normal use |
All TOSHIBA VF-AS1 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in these manuals
What must be done before wiring or inspection?
Turn off the input power, wait at least 15 minutes and confirm the charge lamp is off, then use a meter rated for DC 800 V or more to confirm the DC circuit voltage between PA and PC is 45 V or less.
What loads can the inverter be used with?
It is intended for variable-speed operation of general-purpose industrial three-phase induction motors; it must not be used with other loads, and use as a permanent magnet motor drive requires a matching test in advance.
Which communication protocols are supported by the VF-AS1 series?
The inverter supports the TOSHIBA Inverter Protocol and the MODBUS-RTU Protocol.
From: Toshiba VF-AS1 Series RS485 Communication Function Instruction Manual
What is the default communication protocol setting?
The initial value for the communication protocol selection parameter is set to 0, which corresponds to the TOSHIBA protocol.
From: Toshiba VF-AS1 Series RS485 Communication Function Instruction Manual
What communication protocols are supported by the VF-AS1 series?
The inverter supports the TOSHIBA Inverter Protocol and the MODBUS-RTU Protocol.
From: TOSHIBA VF-AS1 Series RS485 Communication Function Instruction Manual
What is the maximum frame length for RS485 communication?
The frame length is variable, with a maximum of 17 bytes.
From: TOSHIBA VF-AS1 Series RS485 Communication Function Instruction Manual