TOSVERT VF-AS1 series RS485 communication function operation manual, introduces the RS485 communication function of variable frequency drive, including communication port, communication protocol, communication command, communication parameters, computer command and monitoring and other contents.
This Chinese manual describes the RS485 communication function of the Toshiba TOSVERT VF-AS1 Series industrial inverter. It covers the standard 2-wire and 4-wire RS485 ports, computer link operation, and inter-drive communication without a computer.
The document explains data transmission specifications and frame handling, then details the Toshiba inverter protocol and MODBUS-RTU protocol, including ASCII and binary formats, commands, broadcast communication, and error codes. It also covers communication parameters, computer commands and monitoring, parameter data, and appendices for data codes, response time, VF-A7 compatibility, troubleshooting, and RS485 wiring. This manual is written in Chinese.
| Communication baud rate | 9600 / 19200 / 38400 bps; selectable with a parameter |
|---|---|
| Communication protocol | Toshiba inverter protocol / MODBUS-RTU; selectable with a parameter |
| Character transmission (ASCII mode) | JIS X 0201 8-bit (ASCII) |
| Character transmission (binary / MODBUS-RTU) | Fixed 8-bit binary code |
| Stop bit length | Inverter receive: 1 bit; inverter send: 2 bits |
| Parity | Even / odd / none; selectable with a parameter |
| Checksum / CRC | Checksum for Toshiba inverter protocol; CRC for MODBUS-RTU |
| Frame length | Variable, up to 17 bytes |
| Bit transmission order | Low-order bit first |
The manual lists the Toshiba inverter protocol and MODBUS-RTU; it notes that MODBUS-RTU does not support all commands.
9600, 19200, or 38400 bps can be selected with a parameter.
Communication can begin after about two seconds of setting initialization.
The frame length is variable and can be up to 17 bytes.