The battery protection switch box, abbreviated as BCB-BOX (Battery Circuit Breaker Box), is used to connect and disconnect the battery to the UPS system and protect the battery. The manual provides an overview of BCB-BOX, installation, troubleshooting and technical parameters.
The BCB-BOX (Battery Circuit Breaker Box) is an electrical device used to connect and disconnect the battery from the UPS system and to protect the battery. This manual covers two models, PDU8000-0063DCV8-BXA002 (63 A) and PDU8000-0125DCV8-BXA002 (125 A), and is written for marketing, technical support, system, hardware installation, commissioning, data configuration and maintenance engineers.
It describes safety precautions, the product's purpose and model naming, appearance and internal structure including the BIB control board, unpacking inspection, installation tools, environment and cable preparation, wall-mounted and bracket installation, cable connections for one or two battery strings, parameter settings, troubleshooting, replacement of an old BIB board with a new one, technical specifications and acronyms. This manual is written in Chinese.
| Power distribution capacity | 63 A (PDU8000-0063); 125 A (PDU8000-0125) |
|---|---|
| Output voltage level | Rated 600 V DC |
| Recommended UPS power cable | 1×16 mm² (63 A model); 1×35 mm² (125 A model) |
| Expansion bolts supplied (63 A model) | M6×60, 4 pcs |
It is an electrical device that connects and disconnects the battery from the UPS system and protects the battery.
Two models are described: PDU8000-0063DCV8-BXA002 (63 A) and PDU8000-0125DCV8-BXA002 (125 A).
It supports wall mounting and bracket mounting, with cables routed in from the bottom and out through the top.
The installation site must be well ventilated and kept away from water sources, heat sources and flammable or explosive materials.