IC915 NTC/PTC Dual Output Digital Temperature Controller User Manual

IC915 NTC/PTC dual output digital temperature controller manual, introduces the product features, usage methods, parameter settings and other information


IC915 NTC/PTC Dual Output Digital Temperature Controller User Manual - cover page
Category
Temperature monitor
Document type
User Manual
Language
Chinese
Pages
4
File format
PDF
File size
148 KB
Published
30 October, 2023
Updated
30 October, 2023
MD5 checksum
CAD816CDD9147B1E81EC74F9CD60F0AF

About this manual

The IC915 is a dual output digital temperature controller that accepts one PTC or NTC thermistor temperature sensor. This Chinese user manual explains how to set the two temperature setpoints SP1 and SP2, how to configure the two switch outputs OUT1 and OUT2 as heating or cooling, and how the AOL parameter changes the relationship between the setpoints and outputs.

It also describes the five parameter groups rS1, rS2, dIS, CnF and IFPr, the optional copy card for copying parameters between instruments, the user password function, the four front-panel indicator lights and the AL sensor alarm, followed by technical data, wiring notes, operating conditions and the disclaimer. This manual is written in Chinese.

What's inside

  • Setting the temperature setpoints SP1 and SP2
  • Outputs and AOL output modes
  • Parameter setting and parameter groups
  • Copy card
  • Password setting
  • Indicator lights and alarm
  • Technical data
  • Wiring
  • Operating conditions
  • Disclaimer

Specifications

Power supply12 V AC/DC ±10% or 230 V ±10%, 50/60 Hz
Power consumption230 V version: <3 W; 12 V version: <1.5 W
Sensor input1 PTC or NTC thermistor; PTC -50 to +140 °C, NTC -50 to +110 °C
Dimensions74 × 32 × 59 mm
Panel cutout71 × 29 mm
Operating ambient temperature-5 to +55 °C
Operating humidity10 to 90 %RH, non-condensing
HousingResin plastic PC+ABS, UL94 V-0

Frequently asked questions

How do I set the SP1 temperature setpoint?

While the display shows the measured sensor value, press the SZR key; the display shows SP1. Press SZR again to see the current value, change it with the arrow keys, then press FNC to exit.

What happens when parameter AOL is set to 2?

SP2 is hidden automatically and the instrument fixes OUT1 as the cooling output and OUT2 as the heating output, so the HC1 and HC2 settings have no effect.

How do I enter the parameter groups?

Hold the SZR key on the front panel for at least 5 seconds while the measured value is displayed; the first parameter group code rS1 then appears.

What should I check when alarm code AL appears?

Check whether the temperature sensor used matches the A00 parameter value, check the sensor connection to the instrument, and measure the sensor resistance to determine whether it is damaged.

Download PDF (148 KB)