This document is Lapp's VFD Cable Selection Guide, which introduces the AWG size selection, regulatory codes, voltage drop factor and other information of cables
This document serves as a selection guide for Lapp 679 Variable Frequency Drive (VFD) cables. It provides charts to determine the appropriate AWG wire size based on drive horsepower (HP), voltage (230V, 460V, or 575V), and regulatory codes such as NEC Art. 430-122.
The guide includes detailed tables for calculating voltage drop factors over specific distances and offers examples of how to calculate the required AWG size using full load current (FLC) multiplied by 125% per NEC standards.
To calculate the voltage drop, multiply the distance to the motor by the voltage drop factor found in the table.
You must know the motor HP, motor voltage, and full load current (FLC) to calculate the AWG size.
Per NEC, you must multiply the full load current by 125% to calculate the required AWG size.