This manual introduces the features, specifications, wiring, and usage methods of I-7005 and M-7005.
The I-7005 and M-7005 are network data acquisition and control modules featuring 24-bit sigma-delta ADCs for analog-to-digital conversion and digital I/O capabilities. They support thermistor inputs and digital outputs, communicating via an RS-485 bi-directional serial bus using the DCON protocol or Modbus RTU.
| Input Channels | 8 |
|---|---|
| Input Type | Thermistor |
| Sampling Rate | 8 samples/sec |
| Bandwidth | 5.24 Hz |
| Accuracy | ±0.1% |
| Output Channels | 6 |
| Output Type | Open collector |
| Output Load | 30 V, 100 mA max. |
| Power Requirement | +10 to +30 VDC |
| Consumption | 1.1 W |
| Temperature Range | Operating -25°C to +75 °C |
Transmission speeds of up to 115.2 Kbps can be selected.
A warm-up period of 30 minutes is recommended to achieve complete performance results.
The maximum resistance is 204800 ohms for firmware version A3.7 and later.