OMRON G7S Relay With Forcibly Guided Contacts User Manual

The document describes the features and characteristics of relays with forcibly guided contacts conforming to the EN standard, as well as their application in CE marking of machinery and interlocking circuits.


OMRON G7S Relay With Forcibly Guided Contacts User Manual - cover page
Brand
Omron
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
22
File format
PDF
File size
703 KB
Published
04 May, 2012
Updated
29 September, 2023
Model
G7S
MD5 checksum
79E8DA304DB44E03365C0CD6E5839C9D

About this manual

The OMRON G7S series provides relays with forcibly guided contacts that meet EN50205 Class A and VDE certification. The manual details the model variants, electrical ratings, mechanical durability, and available socket accessories for both track‑mounting and back‑mounting applications.

Safety precautions, wiring guidelines, and installation instructions are included to ensure reliable operation in industrial control circuits. The document also lists environmental limits, handling recommendations, and warranty information.

What's inside

  • Specifications
  • Safety Precautions
  • Mounting and Sockets
  • Wiring Guidelines
  • Technical Data
  • Troubleshooting
  • Warranty and Liability
  • Application Considerations

Specifications

Power consumption≈ 0.8 W
Contact rating (resistive load)240 VAC 3 A, 24 VDC 3 A
Carry current6 A
Maximum switching voltage250 VAC, 24 VDC
Maximum switching current6 A
Mechanical durability18,000 operations/h
Electrical durability100,000 operations min.
Ambient operating temperature-25 °C to 70 °C
Weight≈ 65 g

Frequently asked questions

What is the maximum switching current the G7S can handle?

The relay can switch up to 6 A of current.

What wire size should be used for connecting the P7S‑14F‑END socket?

Use stranded wire 0.75 mm to 1.5 mm or solid wire 1.0 mm to 1.5 mm in diameter.

What torque is recommended for tightening the socket screws?

Tighten each screw to approximately 0.98 N·m.

Download PDF (703 KB)