Yaskawa VARISPEED-616G5 Error PUF: DC Bus Fuse Open

Yaskawa VARISPEED-616G5 · taken from the manufacturer’s manual, pages cited

Error codePUF

DC Bus Fuse Open means a short circuit to ground has damaged the output transistors, requiring inverter replacement. The manual's first action is: “Investigate the cause, implement corrective actions, then replace the inverter.”

Model
Yaskawa VARISPEED-616G5
Display shows
DC Bus Fuse Open (PUF)
Type
Error code
Source
Manual p. 274

What PUF means

DC Bus Fuse Open p. 274

Common causes

  • Due to a short circuit to ground on the inverter output side, the output transistors are damaged; (check whether the following terminals are shorted—if they are, the transistors are damaged: B1(⊕3) ↔ U, V, W ⊕ ↔ U, V, W). p. 274

What to do

  1. Investigate the cause, implement corrective actions, then replace the inverter. p. 274

Before you service the product, read the safety instructions in the manual p. 4.

If PUF is still not resolved

  • contact Yaskawa customer service p. 4
    “有触电和火灾的危险。”
  • contact Yaskawa customer service p. 6
    “有触电的危险。”

This page summarises what the manufacturer’s manual says about PUF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.