Error codeOC
Overcurrent means there is a short circuit to ground on the inverter output side, or the load is too large or acceleration time is too short. The manual's first action is: “Investigate the cause, implement corrective actions, then reset.”
- Model
- Yaskawa VARISPEED-616G5
- Display shows
- Overcurrent (OC)
- Type
- Error code
- Source
- Manual p. 274
What OC means
Overcurrent p. 274
Common causes
- A short circuit to ground on the inverter output side (motor burned out, insulation degradation, cable damage causing contact, grounding, etc.). p. 274
- Load is too large, acceleration time is too short. p. 274
- Using a special motor or a motor exceeding the maximum applicable power. p. 274
- The inverter output side contactor has opened as an interlock action. p. 274
What to do
- Investigate the cause, implement corrective actions, then reset. p. 274
Before you service the product, read the safety instructions in the manual p. 4.
If OC is still not resolved
This page summarises what the manufacturer’s manual says about OC; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.