Yaskawa VARISPEED-616G5 Error GF: Ground Fault

Yaskawa VARISPEED-616G5 · taken from the manufacturer’s manual, pages cited

Fault codeGF

Ground Fault means there is a ground short circuit on the inverter output side. The manual's first action is: “Investigate the cause, implement corrective actions, then reset.”

Model
Yaskawa VARISPEED-616G5
Display shows
Ground Fault (GF)
Type
Fault code
Source
Manual p. 274

What GF means

Ground Fault p. 274

Common causes

  • A ground short circuit on the inverter output side (motor burned out, insulation degradation, cable damage causing contact, grounding, etc.). p. 274

What to do

  1. Investigate the cause, implement corrective actions, then reset. p. 274

Before you service the product, read the safety instructions in the manual p. 4.

If GF is still not resolved

  • contact Yaskawa customer service p. 4
    “有触电和火灾的危险。”
  • contact Yaskawa customer service p. 6
    “有触电的危险。”

This page summarises what the manufacturer’s manual says about GF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.