Error codePF
Input Phase Loss means there is a phase loss on the input power supply, a momentary power outage, or loose input terminals. The manual's first action is: “Investigate the cause, implement corrective actions, then reset.”
- Model
- Yaskawa VARISPEED-616G5
- Display shows
- Input Phase Loss (PF)
- Type
- Error code
- Source
- Manual p. 274
What PF means
Input Phase Loss p. 274
Common causes
- Phase loss on the input power supply. p. 274
- A momentary power outage occurred. p. 274
- Input power supply terminals are loose. p. 274
- Input voltage fluctuates excessively. p. 274
- Inter‑phase voltage imbalance is severe. p. 274
What to do
- Investigate the cause, implement corrective actions, then reset. p. 274
Before you service the product, read the safety instructions in the manual p. 4.
If PF is still not resolved
This page summarises what the manufacturer’s manual says about PF; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Yaskawa. Found a mistake? Report an error.