Error codeOP2
The deceleration time dEL is too short, the dynamic braking resistor has considerably large resistance, or dynamic braking resistor is OFF with overvoltage limit operation F3.5 OFF. The manual's first action is: “Increase the deceleration time dEL.”
- Model
- Toshiba VF-AS1
- Display shows
- Overvoltage during deceleration (OP2)
- Type
- Error code
- Source
- Manual p. 296
What OP2 means
Overvoltage during deceleration p. 296
Common causes
- The deceleration time dEL is too short(regenerative energy is too large). p. 296
- The dynamic braking resistor has a considerably large resistance. p. 296
- Dynamic braking resistor is OFF. Overvoltage limit operation F3.5 is OFF. p. 296
- The input voltage fluctuates abnormally (1)The power supply has a capacity of 500kVA or more. (2)A power factor improvement capacitor is opened and closed. (3)A system using a thyristor is connected to the same power distribution line. p. 296
What to do
- Increase the deceleration time dEL. p. 296
- Install a dynamic braking resistor. p. 296
- Decrease dynamic braking resistance. (Also reset the Pbr.) p. 296
- Set overvoltage limit operation F3.5 properly. Insert a suitable input reactor. p. 296
Before you service the product, read the safety instructions in the manual p. 17.
If OP2 is still not resolved
- Read the Instruction Manual p. 17 “Read the Instruction Manual.”
This page summarises what the manufacturer’s manual says about OP2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.