Toshiba VF-AS1 Error OCL: Loaded side overcurrent at start time

Toshiba VF-AS1 inverter · taken from the manufacturer’s manual, pages cited

Error codeOCL

The insulation of the output main circuit or motor is defective, the motor has too small impedance, or the PB-PC+ circuit is shorted. The manual's first action is: “Check the impedance wiring for the resistor, etc.”

Model
Toshiba VF-AS1
Display shows
Loaded side overcurrent at start time (OCL)
Type
Error code
Source
Manual p. 295

What OCL means

Loaded side overcurrent at start time p. 295

Common causes

  • The insulation of the output main circuit or motor is defective. p. 295
  • The motor has too small impedance. p. 295
  • PB-PC+ circuit is shorted. p. 295
  • A resistor with resistance smaller than the minimum allowable resistance is connected. p. 295
  • Parameter Pb was set to 1 or 2 without connecting regenerative brake or with wire disconnected (with dynamic braking). p. 295

What to do

  1. Check the impedance wiring for the resistor, etc. p. 295
  2. Make a service call. p. 295
  3. If regenerative brake is not necessary, set parameter Pb to 0. p. 295

Before you service the product, read the safety instructions in the manual p. 17.

If OCL is still not resolved

  • Read the Instruction Manual p. 17
    “Read the Instruction Manual.”

This page summarises what the manufacturer’s manual says about OCL; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.