The input voltage fluctuates abnormally due to a power supply with 500kVA or more capacity, a power factor improvement capacitor being opened and closed, or a system using a thyristor being connected. The manual's first action is: “Insert a suitable input reactor.”
- Model
- Toshiba VF-AS1
- Display shows
- Overvoltage during acceleration (OP1)
- Type
- Error code
- Source
- Manual p. 296
What OP1 means
Overvoltage during acceleration p. 296
Common causes
- The input voltage fluctuates abnormally (1)The power supply has a capacity of 500kVA or more. (2)A power factor improvement capacitor is opened and closed. (3)A system using a thyristor is connected to the same power distribution line. (4)A restart signal is input to the rotating motor after a momentary stop, etc. p. 296
What to do
- Insert a suitable input reactor. p. 296
Before you service the product, read the safety instructions in the manual p. 17.
If OP1 is still not resolved
- Read the Instruction Manual p. 17 “Read the Instruction Manual.”
This page summarises what the manufacturer’s manual says about OP1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.