Error codeUP1
The input voltage (in the main circuit) is too low or a momentary power failure occurs because undervoltage continues longer than undervoltage detection time F6.2B. The manual's first action is: “Check the input voltage.”
- Model
- Toshiba VF-AS1
- Display shows
- Undervoltage (in main circuit) (UP1)
- Type
- Error code
- Source
- Manual p. 296
What UP1 means
Undervoltage (in main circuit) p. 296
Common causes
- The input voltage (in the main circuit) is too low. p. 296
- Momentary power failure occurs because undervoltage continues longer than undervoltage detection time F6.2B. p. 296
What to do
- Check the input voltage. p. 296
- To cope with a momentary stop due to undervoltage, enable UU5 (Regenerative power ride-through control), UU5 (auto-restart control), and F6.2B (Undervoltage detection time). p. 296
Before you service the product, read the safety instructions in the manual p. 17.
If UP1 is still not resolved
- Read the Instruction Manual p. 17 “Read the Instruction Manual.”
This page summarises what the manufacturer’s manual says about UP1; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.