The input voltage fluctuates abnormally due to a power supply with 500kVA or more capacity, a power factor improvement capacitor being opened and closed, or a system using a thyristor being connected, or the motor is in a regenerative state because the load causes the motor to run at a frequency higher than the inverter output frequency. The manual's first action is: “Insert a suitable input reactor.”
- Model
- Toshiba VF-AS1
- Display shows
- Overvoltage during fixed speed operation (OP3)
- Type
- Error code
- Source
- Manual p. 296
What OP3 means
Overvoltage during fixed speed operation p. 296
Common causes
- The input voltage fluctuates abnormally. (1)The power supply has a capacity of 500kVA or more. (2)A power factor improvement capacitor is opened and closed. (3)A system using a thyristor is connected to the same power distribution line. p. 296
- The motor is in a regenerative state because the load causes the motor to run at a frequency higher than the inverter output frequency. p. 296
What to do
Before you service the product, read the safety instructions in the manual p. 17.
If OP3 is still not resolved
- Read the Instruction Manual p. 17 “Read the Instruction Manual.”
This page summarises what the manufacturer’s manual says about OP3; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.