Toshiba VF-AS1 Error OP3: Overvoltage during fixed speed operation

Toshiba VF-AS1 inverter · taken from the manufacturer’s manual, pages cited

Error codeOP3

The input voltage fluctuates abnormally due to a power supply with 500kVA or more capacity, a power factor improvement capacitor being opened and closed, or a system using a thyristor being connected, or the motor is in a regenerative state because the load causes the motor to run at a frequency higher than the inverter output frequency. The manual's first action is: “Insert a suitable input reactor.”

Model
Toshiba VF-AS1
Display shows
Overvoltage during fixed speed operation (OP3)
Type
Error code
Source
Manual p. 296

What OP3 means

Overvoltage during fixed speed operation p. 296

Common causes

  • The input voltage fluctuates abnormally. (1)The power supply has a capacity of 500kVA or more. (2)A power factor improvement capacitor is opened and closed. (3)A system using a thyristor is connected to the same power distribution line. p. 296
  • The motor is in a regenerative state because the load causes the motor to run at a frequency higher than the inverter output frequency. p. 296

What to do

  1. Insert a suitable input reactor. p. 296
  2. Install a dynamic braking resistor. p. 296

Before you service the product, read the safety instructions in the manual p. 17.

If OP3 is still not resolved

  • Read the Instruction Manual p. 17
    “Read the Instruction Manual.”

This page summarises what the manufacturer’s manual says about OP3; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.