Toshiba VF-AS1 Error OH2: Thermal trip stop command from external device

Toshiba VF-AS1 inverter · taken from the manufacturer’s manual, pages cited

Error codeOH2

Rapid acceleration is operated, the DC braking amount is too large, or the Vf setting is improper. The manual's first action is: “Increase the acceleration time RLC.”

Model
Toshiba VF-AS1
Display shows
Thermal trip stop command from external device (OH2)
Type
Error code
Source
Manual p. 295

What OH2 means

Thermal trip stop command from external device p. 295

Common causes

  • Rapid acceleration is operated. p. 295
  • The DC braking amount is too large. p. 295
  • The Vf setting is improper. p. 295
  • A restart signal is input to the rotating motor after a momentary stop, etc. p. 295
  • The load is too large. p. 295

What to do

  1. Increase the acceleration time RLC. p. 295
  2. Reduce the DC braking amount F25 and the DC braking time F26. p. 295
  3. Check the Vf parameter setting. p. 295
  4. Use U5 (Auto-restart) and U6 (Regenerative power ride-through control). p. 295
  5. Use an inverter with a larger rating. p. 295

Before you service the product, read the safety instructions in the manual p. 17.

If OH2 is still not resolved

  • Read the Instruction Manual p. 17
    “Read the Instruction Manual.”

This page summarises what the manufacturer’s manual says about OH2; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.