The cooling fan does not rotate, the ambient temperature is too high, or the vent is blocked up. The manual's first action is: “Restart the operation by resetting the inverter after it has cooled down enough.”
- Model
- Toshiba VF-AS1
- Display shows
- OCR
- Type
- Error code
- Source
- Manual p. 295
What OCR means
Dynamic braking element overcurrent (200V-55kW or larger, 400V-90kW or larger) p. 295
Common causes
- The cooling fan does not rotate. p. 295
- The ambient temperature is too high. p. 295
- The vent is blocked up. p. 295
- A heat generating device is installed close to the inverter. p. 295
- The thermistor in the unit is disconnected. p. 295
What to do
- Restart the operation by resetting the inverter after it has cooled down enough. p. 295
- The fan requires replacement if it does not rotate during operation. p. 295
- Secure sufficient space around the inverter. p. 295
- Do not place any heat generating device near the inverter. p. 295
- Make a service call. p. 295
Before you service the product, read the safety instructions in the manual p. 17.
If OCR is still not resolved
- Read the Instruction Manual p. 17 “Read the Instruction Manual.”
This page summarises what the manufacturer’s manual says about OCR; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Toshiba. Found a mistake? Report an error.