Error, fault and alarm codes of products - what each code means, its causes and what to do - read from the manufacturers’ manuals, with the manual page each answer comes from.
The power unit has detected line asymmetry on the DC link voltage, possibly from phase failure or incorrect wiring in the motor or line connections. The manual's first action is: “- check the line phase connection. - …
The braking chopper has experienced an overcurrent condition, which may be due to a short circuit in the braking resistor or improper sizing of the external resistor. The manual's first action is: “- check whether the…
The power unit has detected air intake overtemperature, indicating the cooling system is overheating and requires shutdown. The manual's first action is: “OFF 1 (OFF2)”
The power unit has detected an internal overtemperature that exceeds its alarm threshold, which may escalate to a more severe fault if temperatures continue rising. The manual lists no action for this code.
Hardware current limiting has been triggered for phase W, likely due to incorrect parameterization or motor/power cable faults. The manual lists no action for this code.
The Lq-Ld measurement failed due to issues with current ratios or harmonic levels in the system. The manual's first action is: “Fault value (r0949, interpret decimal): 10: Stage 1: The ratio between the measured curre…
An error occurred during the pole position identification routine, requiring a POWER ON reset for troubleshooting. The manual's first action is: “Only for internal Siemens troubleshooting. Carry out a POWER ON.”
No motor is detected after enabling inverter pulses, possibly due to incorrect setup or motor failure. The manual lists no action for this code.
The motor temperature or model 2 temperature has exceeded the alarm threshold, triggering a response based on parameterized settings. The manual lists no action for this code.
An external fault condition has been triggered as defined by parameter p2106. The manual's first action is: “Eliminate the causes of this alarm.”
An external alarm condition has been triggered as defined by parameter p2112. The manual's first action is: “Eliminate the causes of this alarm.”
No rated data are stored in the power unit EEPROM, requiring replacement or customer service contact. The manual's first action is: “Replace the power unit or inform Siemens Customer Service.”
The motor temperature sensor has failed due to wire breakage or disconnection exceeding resistance thresholds. The manual lists no action for this code.
An error occurred while evaluating the temperature sensor set in p0601, with a timer starting to detect persistent faults. The manual lists no action for this code.
There is an error in the configuration of the motor temperature model, preventing it from being saved. The manual lists no action for this code.