The ovd code indicates Overvoltage at Deceleration, where during deceleration the AC motor drive detected an overvoltage on the internal high-voltage DC side. The manual's first action is: “Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional).”
- Model
- Delta VFD110CT43F21A3
- Display shows
- Overvoltage at Deceleration (ovd)
- Type
- Error code
- Source
- Manual p. 297
What ovd means
Overvoltage at Deceleration p. 297
Common causes
- During deceleration, the AC motor drive detected an overvoltage on the internal high‑voltage DC side. 460 V: 900 Vdc. p. 297
What to do
- Check that the input voltage is within the drive’s rated input range and monitor for voltage spikes. If the overvoltage is caused by motor inertia regeneration voltage, you can lengthen the deceleration interval or install a braking resistor (optional). p. 297
Before you service the product, read the safety instructions in the manual p. 291.
If ovd is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.
This page summarises what the manufacturer’s manual says about ovd; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.