Delta VFD110CT43F21A3 Error ocn: Overcurrent at Constant Speed

Delta VFD110CT43F21A3 · taken from the manufacturer’s manual, pages cited

Error codeocn

The ocn code indicates Overcurrent at Constant Speed, where overcurrent is generated during operation and output current exceeds three times the VFD's rated current during constant-speed run. The manual's first action is: “Check whether the U‑V‑W wiring to the motor has poor insulation; lengthen deceleration time; replace with a larger‑capacity AC motor drive.”

Model
Delta VFD110CT43F21A3
Display shows
Overcurrent at Constant Speed (ocn)
Type
Error code
Source
Manual p. 297

What ocn means

Overcurrent at Constant Speed p. 297

Common causes

  • Overcurrent generated during operation; during constant‑speed run, output current exceeds three times the VFD's rated current. p. 297

What to do

  1. Check whether the U‑V‑W wiring to the motor has poor insulation; lengthen deceleration time; replace with a larger‑capacity AC motor drive. p. 297

Before you service the product, read the safety instructions in the manual p. 291.

If ocn is still not resolved

The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.