Overcurrent at Deceleration indicates overcurrent during deceleration when output current exceeds three times the VFD's rated current. The manual's first action is: “Check whether the U‑V‑W wiring to the motor has poor insulation; lengthen deceleration time; replace with a larger‑capacity AC motor drive.”
- Model
- Delta VFD110CT43F21A3
- Display shows
- Overcurrent at Deceleration (ocd)
- Type
- Error code
- Source
- Manual p. 297
What ocd means
Overcurrent at Deceleration p. 297
Common causes
- Overcurrent generated during deceleration; during deceleration, output current exceeds three times the VFD's rated current. p. 297
What to do
- Check whether the U‑V‑W wiring to the motor has poor insulation; lengthen deceleration time; replace with a larger‑capacity AC motor drive. p. 297
Before you service the product, read the safety instructions in the manual p. 291.
If ocd is still not resolved
The manual gives no further instruction for this code. Open the code table in the PDF or contact Delta service.
This page summarises what the manufacturer’s manual says about ocd; each statement links to the page it comes from, and quoted lines are copied word for word. It is not a substitute for the manual or for a qualified installer. ManualLib is not affiliated with Delta. Found a mistake? Report an error.
